CALCULATION OUTPUT
Compare the reaction and effective bearing area, with the engineering limits visible.
Choose a rectangular, square or round effective bearing area. Enter the applicable individual outrigger reaction in kN or tonne-force, and the allowable ground bearing pressure supplied by the site assessment. Use the effective dimensions that can transfer load, which may differ from the nominal mat dimensions.
A larger nominal pad does not necessarily provide full ground contact or sufficient structural strength. Do not estimate the reaction by dividing the total crane mass by four.
Enter project-specific values in the form below. Blank or out-of-range inputs stop the calculation. Reset restores an illustrative example, not verified project data. Keep the input sources, assumptions and worked calculation with the result when exporting the PDF.
Rectangle: A = length × width. Square: A = side². Round: A = π × diameter² / 4. q_avg = R / A. A_min = R / q_allow. 1 tf = 9.80665 kN.With reaction R in kN and effective area A in m², average pressure q_avg is in kPa. The theoretical minimum area A_min is an arithmetic requirement for the entered allowable pressure only. The entered allowable pressure and reaction must use a compatible assessment basis; do not mix allowable-pressure and partial-factor design values without engineering review.
Assumes full, uniform effective contact. The model does not calculate the crane reaction or check pad thickness, bending, shear, punching, stiffness, voids, slope, settlement or ground layers. ASME blocking requirements require separate assessment; an area calculation does not verify them.
Effective contact area: 4 m²; average bearing pressure: 75 kPa; theoretical minimum area: 3 m²; pressure / entered limit: 75%.
A 2 m square has the same area. A 2 m diameter circle has an area of 3.141593 m² and, under the same reaction, an average pressure of 95.492966 kPa.
Illustrative values only. This example is not equipment selection or a recommended operating arrangement.

CALCULATION OUTPUT
Confirm the reaction for the actual crane, outrigger extension, lifting sector, load, radius and configuration. Ground assessment and the design of blocking or mats must address load transfer and structural strength. A pressure below the entered limit is an arithmetic comparison, not approval of the lift or the ground.
Related tools: crane chart utilisation · boom geometry.
Planning information, not lift approval. Confirm applicable Malaysian and project requirements with the responsible parties. No appointment or booking is made automatically.
The numeric equations are engineering geometry or an average-pressure model. They are not a certification of compliance or DOSH approval. ASME B30.5-2018 §5-3.2.1.5(i)(1)–(2) addresses blocking strength against crushing, bending and shear, and dimensions adequate for the float and load transfer. Those verified requirements do not prescribe this calculator's area equation or demonstrate pad strength.
Check the edition and clauses required by the project. These sources belong to the requested standards families. A publisher listing alone does not establish that a particular calculation is compliant.